Capacity
of the
UPS : 15
kVA
Load
(Autonomy) : 15 kVA
Cos
Phi : 0.85
Autonomy
: 180 Minutes
(at 100% load)
Nominal
DC Voltage : 220 V
Float DC
Voltage
: 243 V
Minimum DC
Voltage : 194.40 V
Float voltage per
cell
: 2.25 V
Inverter
Efficiency
:
88.00 %
Life Time
Battery
: 25 years
CALCULATION OF SIZING
THE BATTERY
Number of cells
Float DC
Voltage
N =
-----------------------------
Float Voltage per cell
N = 243 /
2.25 = 108 cell
Power Input to Inverter
Load x
Cos Phi
Pinv = -----------------------
Inverter Efficiency
Pinv = 12750/ 0.880 = 14488.64 W
Minimum allowable voltage per cell
Minimum DC Voltage
Vmin = -----------------------------------
Total amount of cells
Total amount of cells
Vmin = 194.4/ 108 = 1.80 Vpc
Discharge current maximum at 100% load.
Pinv *1
Idisc = -----------------------------------
Minimum DC Voltage
Minimum DC Voltage
Idisc = 14488,64/ 194.4 = 74.53
A
Considering Ageing factor (1.25) and Design Margin (1.15):
Idisc =
Idisc x Ageing Factor x Design Margin = 107.14 A
According to Datasheet from GNB-Exide Absolyte GP (attached), that for discharged
constant c = 107.14
A with back up time 180 (One Hundred and Eighty) minutes, end voltage
1.8 Vpc, the battery type to be used is 6-90G11 (432 AH/8 Hrs). No. of cell 108 cells. (=18 blocks)